Cable Branch Projects
Cable line is segmented and T-connected, replacing the traditional cable branch box, with switch protection and remote monitoring..

Residential Power Distribution
High-rise and large-scale residential quarters distribute power, and the ring network is powered by dual power sources to ensure residents’ electricity consumption.

Airports & Railways
Transportation hub, railway distribution station etc…

Conditions of use
◆ Temperature :-25~45℃
◆ Max daily temperature: 35℃
◆ IP degree:Charged body seal IP67, switch cabinet shell IP4x
◆The surrounding air of Environmental friendly gas insulate switchgear cabinet should not be obviously polluted by corrosive combustible gas and water vapor.
◆There is no frequent violent vibration place, and the harshness design under harsh parts meets various requirements.
Standards
KXHB-12 type Environmental friendly gas insulate switchgear cabinet meets the standards below
◆Common technical requirements of GB/T 1022 standards for high-voltage switchgear and controlgear.
◆ GB/T39063640.5kV AC metal enclosed switchgear and control equipment.
◆ GB/T1985 High-voltage AC isolating switch and grounding switch
◆ GB/T38043.6-40.5kV AC high-voltage load switch
◆ GB/T1984 High-voltage AC circuit breaker
◆ GB/T4208 IP code of shell protection level
◆ GB/T7354 Partial Discharge Measurement
◆ GB/T311.1 Insulation coordination Part 1: Definition, principles and rules
Technical Parameters
◆ Circuit breaker Cabinet
| Item | Unit | Data | |||
|---|---|---|---|---|---|
| Rated Voltage | KV | 12 | |||
| Rated Frequency | HZ | 50 | |||
| Rated insulate level | 1Min working frequency withstand Voltage |
To groud,phase to phase | KV | 42 | |
| Break | 48 | ||||
| Lighting impulse withstand voltage(peak) | To groud,phase to phase | KV | 75 | ||
| Break | 85 | ||||
| 1min power frequency withstand voltage of auxiliary/control circuit (to ground) | KV | 2 | |||
| Rated Current | A | 630 | |||
| Rated short-term withstand current(virtual value) | Main circuit/Earthing switch | kA | 25/4s | ||
| Earthing circuit | kA | 21.7/4s | |||
| Rated peak withstand current | Main circuit/Earthing switch | kA | 63 | ||
| Earthing circuit | kA | 54.5 | |||
| Rated short circuit break current and times | kA/Time | 25/30 | |||
| Rated short circuit closing current (peak) | kA | 63 | |||
| Rated cable charging break current | A | 25 | |||
| Rated operating sequence of the breaker O-0.3s-CO-180s-CO | |||||
| Mechanical life | Breaker /Disconnector | Time | 10000/3000 | ||
| IP degree | Sealed box | IP67 | |||
| Switchgear shell | IP4X | ||||
| Gas voltage | Rated gas charging level (20℃, gauge voltage) | Mpa | 0.02 | ||
| Rated gas Min function level (20℃, gauge voltage) | Mpa | 0 | |||
| Sealing performance, | Annual leakage rate | %/Year | ≤0.05 | ||
◆Load switch cabinet
| Item | Unit | Data | |||
|---|---|---|---|---|---|
| Rated Voltage | KV | 12 | |||
| Rated Frequency | HZ | 50 | |||
| Rated insulate level | 1Min working frequency withstand Voltage |
KV | |||
| Lighting impulse withstand voltage(peak) | KV | ||||
| 1min power frequency withstand voltage of auxiliary/control circuit (to ground) | KV | 2 | |||
| Rated Current | A | 630 | |||
| Rated short-term withstand current(virtual value) | Main circuit/Earthing switch | KA | 25/4s | ||
| Earthing circuit | KA | 21.7/4s | |||
| Rated peak withstand current | Main circuit/Earthing switch | KA | 63 | ||
| Earthing circuit | KA | 54.5 | |||
| Rated short circuit closing current (peak) | Load switch/Earthing switch | KA | 63 | ||
| Rated active load interrupting current | A | 630 | |||
| Rated closed-loop interrupting current | A | 630 | |||
| 5% Rated active load interrupting current | A | 31.5 | |||
| Rated cable charging break current | A | 10 | |||
| Rated active load break times | Time | 100 | |||
| Ground fault current breaking | A/Time | 31.5/10 | |||
| The charging current of lines and cables is disconnected under the condition of ground fault. | A/Time | 17.4/10 | |||
| Mechanical life | Breaker /Disconnector | A/Time | 10000/3000 | ||
| IP degree | Sealed box | IP67 | |||
| Switchgear shell | IP4X | ||||
| Gas voltage | Rated gas charging level (20℃, gauge voltage) | Mpa | 0.02 | ||
| Rated gas Min function level (20℃, gauge voltage) | Mpa | 0 | |||
| Sealing performance, | Annual leakage rate | %/Year | ≤0.05 | ||
Typical scheme combination 1

Typical scheme combination 2

Note: The above typical combination reference scheme can be combined in various ways according to the needs of users.
ATS segmentation scheme

Switch operating instructions
Switch position, state and interlock

Operation steps:
Power transmission:Hang (close) the upper and lower doors with a circuit breaker (load switch) → the grounding switch with an isolating switch → the circuit breaker (load switch) with a power transmission is completed.
Power cut:Breaker (load switch) → disconnector → earthing switch → breaker (load switch) is unloaded (opened) and the door is blacked out.
Installation instructions
◆Foundation and overall dimensions

◆Cabinet and overall installation dimensions