New Energy Power Stations
Ground photovoltaic and agro-optical complementary power station: 35kV collecting lines are collected, and 35kV cables of multiple photovoltaic subarrays are collected and sent to the main booster station; One in and one out, scattered points and branches.

Industrial Parks & Mining
35kV distribution network in large chemical, metallurgical, mining and cement plants, with 35kV cable branches in the plant to supply power to many workshops and substations.

Transportation Infrastructure
Branch nodes of 35kV outgoing cables in main substations of high-speed railway station and large subways.

Using Conditions of The 35kV Outdoor Cable Box
Ambient temperature of the35kV Outdoor Cable Box: -30~40℃
Wind speed: equivalent to 34m/s and not more than 700Pa
Humidity: the average daily relative humidity is not more than 95%
The average monthly relative humidity is not more than 95%
Shockproof: the horizontal acceleration is not more than 0.4m/s², and the vertical acceleration is not more than 0.15m/s²
Inclination of 135kV Outdoor Cable Box installation site: Less than 3
Installation environment: The surrounding air should not be obviously polluted by corrosive, combustible gas, water vapor, etc., and the installation site should not be violently vibrated.
○ 35kV Outdoor Cable Box installation and operation and maintenance
◆Installation requirements
Cable stripping and cutting: accurately match the joint specifications (error 1 mm) to avoid damaging the insulation layer.
▶Connector installation: Clean the contact surface and apply silicone grease to prevent oxidation. Tighten with a torque wrench (for example, T-joint needs 35 ~ 40N m).
▶Grounding: The box and cable shield must be reliably grounded (grounding resistance ≤4Ω).
◆Safe operation
▶Check the electricity after power failure, and wear insulating gloves and goggles when operating.
▶Make sure that the grounding switch is closed (if any) before plugging and unplugging the connector.
◆Maintenance suggestion
▶Annual inspection: infrared temperature measurement (focusing on monitoring the temperature rise of joints).
▶Seal inspection: replace the sealing ring once every five years (moisture and dust proof).
▶Insulation test: conduct a withstand voltage test every 3 years.
Order number description of the 35kV Outdoor Cable Box

Technical parameter of the 35kV Outdoor Cable Box
| Rated Voltage | 35KV |
|---|---|
| Rated current | 630A |
| Dynamic stable current | 50KA/0.3s |
| Heat stable current | 20KA/0.3s |
| 1min working frequency withstand voltage | 42KV |
| 15 mins DC Withstand voltage | 52KV |
| Lighting impulse withstand voltage | 105KV |
| Shell IP degree | IP33 |