35KV Outdoor Cable Box

Outdoor Cable Box, which is specially produced by Kexun, a supplier of power transmission and distribution equipment in China, is a cable engineering equipment widely used in power distribution system in recent years. Its main features are bidirectional door opening and the use of wall bushing as the connecting bus bar. Generally, the rated current 630A bolt is used to fix the connecting cable connector, which conforms to DIN47636 standard.

Category:

New Energy Power Stations

Ground photovoltaic and agro-optical complementary power station: 35kV collecting lines are collected, and 35kV cables of multiple photovoltaic subarrays are collected and sent to the main booster station; One in and one out, scattered points and branches.

35KV Outdoor Cable Box

Industrial Parks & Mining

35kV distribution network in large chemical, metallurgical, mining and cement plants, with 35kV cable branches in the plant to supply power to many workshops and substations.

35KV Outdoor Cable Box

Transportation Infrastructure

Branch nodes of 35kV outgoing cables in main substations of high-speed railway station and large subways.

35KV Outdoor Cable Box

Using Conditions of The 35kV Outdoor Cable Box

Ambient temperature of the35kV Outdoor Cable Box: -30~40℃

Wind speed: equivalent to 34m/s and not more than 700Pa

Humidity: the average daily relative humidity is not more than 95%

The average monthly relative humidity is not more than 95%

Shockproof: the horizontal acceleration is not more than 0.4m/s², and the vertical acceleration is not more than 0.15m/s²

Inclination of 135kV Outdoor Cable Box installation site: Less than 3

Installation environment: The surrounding air should not be obviously polluted by corrosive, combustible gas, water vapor, etc., and the installation site should not be violently vibrated.

○ 35kV Outdoor Cable Box installation and operation and maintenance

◆Installation requirements

Cable stripping and cutting: accurately match the joint specifications (error 1 mm) to avoid damaging the insulation layer.

▶Connector installation: Clean the contact surface and apply silicone grease to prevent oxidation. Tighten with a torque wrench (for example, T-joint needs 35 ~ 40N m).

▶Grounding: The box and cable shield must be reliably grounded (grounding resistance ≤4Ω).

◆Safe operation

▶Check the electricity after power failure, and wear insulating gloves and goggles when operating.

▶Make sure that the grounding switch is closed (if any) before plugging and unplugging the connector.

◆Maintenance suggestion

▶Annual inspection: infrared temperature measurement (focusing on monitoring the temperature rise of joints).

▶Seal inspection: replace the sealing ring once every five years (moisture and dust proof).

▶Insulation test: conduct a withstand voltage test every 3 years.

Order number description of the 35kV Outdoor Cable Box

35KV Outdoor Cable Box

Technical parameter of the 35kV Outdoor Cable Box

Rated Voltage 35KV
Rated current 630A
Dynamic stable current 50KA/0.3s
Heat stable current 20KA/0.3s
1min working frequency withstand voltage 42KV
15 mins DC Withstand voltage 52KV
Lighting impulse withstand voltage 105KV
Shell IP degree IP33
Cum sociis natoque penatibus

Purus in mollis nunc sed id semper risus. Velit laoreet id donec ultrices. Tellus pellentesque eu tincidunt tortor. Cum sociis natoque penatibus et. Vitae elementum curabitur vitae nunc sed velit. Nulla pellentesque dignissim enim sit amet venenatis urna cursus eget.

Mattis enim ut tellus elementum

Dolor morbi non arcu risus quis. Quisque non tellus orci ac auctor augue mauris augue. Ipsum a arcu cursus vitae congue mauris rhoncus aenean.

  • Cum sociis natoque penatibus et
  • Aliquam eleifend mi in nulla posuere
  • Ullamcorper malesuada proin libero
  • Purus in mollis nunc sed id

Reviews

There are no reviews yet.

Be the first to review “35KV Outdoor Cable Box”

Your email address will not be published. Required fields are marked *